connection to plc "S7 1500" cannot be established or lasts too long by S7 driver

Right now it is a known behaviour when S7 driver tries to establish a connection to the plc S7-1500.

It can last some time (sometimes up to several minutes).

In this case set the config entry [s7] UseConnections = 1 and start the driver once again.

Using this config entry the time to establish a connection to the plc can be decreased.

 

Date added:
Last revised:
Hits:
8.314
Rating:
Rating: 0.0. 0 vote(s). No rating done at all.
Your vote was '' (0 of 5) You are an anonymous user.
You may log on to do personalized votings
Click the rating bar to rate this item Please log on to do ratings
  • Notification

    FE user cannot be identified! (1403201096)

  • Information

    Not already rated (1403203414)