Important configuration for PLC S7-1500 with TIA Portal

To be able to get a proper connection between WCCOAs7 driver and the new PLC S7-1500 some settings within the TIA Portal engineering tool (e.g. V12 or V13) have to be set.

1. Option "Permit access with PUT/GET communication from remote partner (PLC, HMI, OPC, ...) has to be activated. It can be found at the concerning CPU device/Properties/General/Web server/Protection/Connection mechanisms.

2. The data blocks that WinCC OA to have access to, must be Global DBs. Also optimized block access has to be deactivated.