PVSS00event - IMPL/WARNING - AlertPair, initState, wrong sum alert state --> repaired

Enclosed you'll find the explanation for a log-message which can occur during startup of the project. The log-message is written to the PVSS_II.log-file.


PVSS00event (0), 2012.02.21 17:52:49.432, IMPL, WARNING, 54, Unexpected state, AlertPair, initState, wrong sum alert state --> repaired
System1:Pump1.status:_alert_hdl.._state (Type: 200 Sys: 1 Dp: 3148 El: 23 : _alert_hdl.._state) AlertTime: 2012.02.21;13:17:35:562 Count: 0


Log-message with symbolic names:

PVSS00event (0), <TIMESTAMP>, IMPL, WARNING, 54, Unexpected state, AlertPair, initState, wrong sum alert state --> repaired
<DPE-name>:_alert_hdl.._state (<DP-ID>: _alert_hdl.._state) AlertTime: <alert-time> Count: 0


The log-message desribes that an inconsistency at the alerts was detected during startup of the event-manager. The inconsistency is repaired in the process-image of the event-manager.
If the alert is raised again during runtime or deactivated/activated once the log-message does not occur at the next startup.

Date added:
Last revised:
Hits:
8.573
Rating:
Rating: 3.5. 82 vote(s).
82 anonymous votes
No rating done at all.
Your vote was '' (0 of 5) You are an anonymous user.
You may log on to do personalized votings
Click the rating bar to rate this item Please log on to do ratings
  • Notification

    FE user cannot be identified! (1403201096)