PVSS00event - PARAM/WARNING - Element does not exist, EvManager, connectCopyDps
Enclosed you'll find the explanation for a log-message which can occur during startup of the event-manager. The log-message is written to the PVSS_II.log-file.
PVSS00event (0), 2012.10.10 08:31:54.233, PARAM,WARNING, 8, Element does not exist, EvManager, connectCopyDps, _PLC13.Active
Log-message with symbolic names:
PVSS00event (0), 2012.10.10 08:31:54.233, PARAM,WARNING, 8, Element does not exist, EvManager, connectCopyDps, <DP-element>
This log-message describes that the config-entry copyDp was defined for a non existing DP-element. The copyDp-functionality will not be called for the given DP-element, this could lead to an incorrect behaviour in your project.
The config-entry can be defined in the config, config.level or config.redu-file in your project or any of the sub-projects including the config.level and config.redu file for the installed version.
Please check if the config-entry is necessary in your project.
If it is needed you have to create the datapoint to avoid this error and ensure the correct functionality.