PVSS00event - PARAM/WARNING - SumAlert config does not have an id list nor an id pattern to select DP elements

Enclosed you will find the explanation for a log-massage during system start concerning duplicate elements. The log-message is written to the PVSS_II.log-file.

PVSS00event (0), 2011.01.17 08:41:28.186, PARAM,WARNING, 22, Internal consistency check for config failed, DP: dist_4:MOT_MOT_-_TERMINAL_INTERFACE_FACILITY_PIG_RECEIVER_RP-1301_1_1.Warning:_alert_hdl, MAN: (SYS: 4 Event -num 0 CONN: 1), SumAlert config does not have an id list nor an id pattern to select DP elements


Log-message with symbolic names:

PVSS00event (0), 2011.01.17 08:41:28.186, PARAM,WARNING, 22, Internal consistency check for config failed, <DP-name>, MAN: (SYS: <system number> Event -num 0 CONN: 1), SumAlert config does not have an id list nor an id pattern to select DP elements

 

The configuration of the alert_hdl-config of the appropriate datapoint is not correct. There is no DP-list or DP-pattern assigned to a sumalert. This sumalert will be ignored internally.
 