WCCILevent - IMPL/WARNING - Could not connect the parameters, please check the dpFunction

Enclosed you'll find the explanation for a log-message which can occur during startup. The log-message is written to the PVSS_II.log-file.

WCCILevent (0), 2015.02.13 10:03:54.573, IMPL, WARNING, 54, Unexpected state, DP: System1:Engine_1.status:_dp_fct, MAN: (SYS: 1 Event -num 0 CONN: 1), Could not connect the parameters, please check the dpFunction


Log-message with symbolic names:

WCCILevent (0), <TIMESTAMP>, IMPL, WARNING, 54, Unexpected state, DP: <DPE-name>:_dp_fct, MAN: (SYS: 1 Event -num 0 CONN: 1), Could not connect the parameters, please check the dpFunction


The log-messages describes that the configuration of the datapoint function at the given dp-element is not correct. The datapoint elements which are defined as input parameters are not exisiting and therefore the connect is not possible.

Please check the configuration of the datapoint function and correct it to get rid of this error.
When opening the configuration panel for the datapoint function in the para module you might again a log-message which describes that the DPE-ID cannot be resolved to a DPE-name.

WCCOAui (manager number), <TIMESTAMP>, IMPL, WARNING, 54, Unexpected state, DpIdentifier, formatValue, could not convert DpIdentifier to string: (<DPE-ID>: _original.._value)

In the panel the entries with missing datapoints are displayed only with the parameter-name (e.g. p3) and the “=”-character. The DPE-name is displayed as empty string.

Date added:
Last revised:
Hits:
12.388
Rating:
Rating: 3.3. 71 vote(s).
71 anonymous votes
No rating done at all.
Your vote was '' (0 of 5) You are an anonymous user.
You may log on to do personalized votings
Click the rating bar to rate this item Please log on to do ratings
  • Notification

    FE user cannot be identified! (1403201096)

Tags:
PVSS, WinCC Open Architecture