WCCOAbacnet (), , SYS, SEVERE, 54, Unexpected state, BACnet Error: SubscribeCOV Class=Services: Code=COV Subscription Failed; COV Subscribe response for 8-17-7—1

In some cases (for example: if a Device doesn't support the COV(cause of value)-service), it could happen, that the BACnet-driver is not able to make COV-subscriptions.

In that cases, the following error message will be displayed in the logviewer (example):

WCCOAbacnet (1), 2014.02.19 12:17:01.635, SYS,  SEVERE,     54, Unexpected state, BACnet Error: SubscribeCOV Class=Services: Code=COV Subscription Failed; COV Subscribe response for 8-17-7—1<o:p></o:p>

 

To find out, which of the configured devices/instance are affected, the last digit combination of this log-message can be interpreted like described below:

<device identifier> - <object type> - <object instance> -- <driver number>

The example log-output (see above) therefore means the following:

8-17-7---1    =>    device identifier = 8    object type = 17 (scheduler)     object instance = 7     driver number = 1

 

The object type mapping can be checked within the following file:

<WinCCOA-Version-Dir>\data\bacnet\BACNet_objecttype_mapping.cat

 

Date added:
Last revised:
Hits:
10.492
Version:
ALL Versions
Rating:
Rating: 0.0. 0 vote(s). No rating done at all.
Your vote was '' (0 of 5) You are an anonymous user.
You may log on to do personalized votings
Click the rating bar to rate this item Please log on to do ratings
  • Notification

    FE user cannot be identified! (1403201096)

  • Information

    Not already rated (1403203414)

Tags:
Engineering, Special Functions / Features, PVSS