Drive2 data point type

This data point type can be used to display a controllable drive. There are four different versions to choose from.

  • Type 1: one ON message (only the address of .state.on is enabled)

  • Type 2: two directions of rotation (addresses .state.on and .state.ccOn are enabled)

  • Type 3: two speeds (addresses .state.on and .state.on_2 are enabled)

  • Type 4: two directions of rotation and two speeds (addresses .state.on and .state.on_2 and .state.ccOn and .state.ccOn_2 are enabled)

Faults and operating mode messages can be displayed as an option. Only .mode.remote and .mode.man must exist. Please refer to the type table for the command code.

Element Data type Description
alert.ControlFuse bool Control fuse fault
alert.converter bool Frequency converter fault
alert.motorSwitch bool Motor protective switch fault
alert.motorTherm bool Fault in motor thermistor protection
alert.overload bool Overload fault
alert.speed bool Speed fault
alert.sumalertPLC bool External group alert
alert.sumalert string Internal group alert
cmd.on int on=1 Off, on=2 On (clockwise rotation), on=4 counter-clockwise rotation, on=8 On clockwise rotation 2nd speed, on=16 counter-clockwise rotation 2nd speed
cmd.mode typref Reference of the MODE_CMD data point type, auto = 2 manual mode, auto = 1 automatic mode
para.speed float Required speed
state.on bool Clockwise rotation
state.ccOn bool Counter-clockwise rotation
state.on_2 bool Clockwise rotation 2nd speed
state.ccOn_2 bool Counter-clockwise rotation 2nd speed
state.off bool Off
state.mode typref Reference of the MODE_STATE data point type
value.powerCon float Power consumption
value.speed float Speed

Associated symbols

Symbol Symbol name Description
Drive This symbol represents a drive
Rotor This symbol represents a rotor (side elevation)
Rotor_Big This symbol represents a rotor (plan view)