WCCIL00event - IMPL/WARNING - EvDpManager::getDpValueAttribut: no config
Enclosed you'll find the explanation of a log-message which can be displayed during startup of the project. The log message is written to the PVSS_II.log-file.
WCCILevent (0), 2012.01.31 16:05:00.002, IMPL, WARNING, 54, Unexpected state, DP: System1:PUMP1.alarm:_original.._stime, MAN: (SYS: 1 Event -num 0 CONN: 2), EvDpManager::getDpValueAttribut: no config
There can also be similar log-messages which have the same cause:
WCCILevent (0), 2012.01.31 16:05:00.002, IMPL, WARNING, 54, Unexpected state, DP: System1:PUMP1.alarm:_original.._default, MAN: (SYS: 1 Event -num 0 CONN: 2), EvDpManager::getDpValueAttribut: no config
This log message occurs when the work function is called for a dpConnect that is made to a data point element that is defined as a structure node. Please check the data point type configuration for the data point specified in the log message. The last elements in a data point structure should always be elements with a "real" data type, e.g. boolean value, integer, ....