CONTROL

Control Keywords

With version 3.16 some new control keywords are reserved (e.g.new or delete, refer to Variables and constants for further information) or used (e.g.struct or class, refer to Control++) byWinCC OA and cannot be used e.g. as variable names anymore. When updating older projects to 3.19, problems can arise if you have defined one of these keywords as a variable name. In this case you have to replace the now invalid names in the respective scripts and panels.

Script Execution

As of version 3.18, functions throw a syntax error in the following cases, which prevents the script from being executed:

  • Functions that are declared as void but still return a value.
  • Functions that have a declared return value but do not return anything.

getFileNames() - dir Parameter

Starting with WinCC OA version 3.16 P001 only a valid folder path can be stated for the dir parameter of the function getFileNames(). Stating an actual file path will return an empty string as the file path is no valid directory.

CNS Functions with Wildcards

SQL Queries - . before UserName

Beginning with version 3.20 the syntax check for SQL queries has been improved, which results in an error message in case of invalid usage of user names (UserName without "." as prefix).

This behavior was not explicitly validated in previous versions.

Wrong usage of user name

sQuery = "SELECT 'UserName:_online.._value' FROM '*' WHERE _DPT = "_Ui"";

Correct syntax of the SQL query

sQuery = "SELECT '.UserName:_online.._value' FROM '*' WHERE _DPT = "_Ui"";