PM Agent Configuration

  • Create a WinCC OA project or use an existing one.
  • In config file add section [PMAgent] and set entry enabled to 1, the other entries are optional:
    [PMAgent]
    enabled = 1
    maxBufferSize="3000"
  • Configure Standard WebServer in config file (https port)
  • In the WinCC OA Console add the Standard WebServer (webclient_http.ctl) using Start Mode "always".
  • Open the Plantmodel Editor and add View(s) and Node(s) as needed.
  • Select node and assign a data point to it (repeat this for all your nodes you've added)
  • Switch to PM Agent tab and configure the PM Tag(s) as needed:
    • Activate the radio box active.
    • Choose Tag Configuration as needed.
  • Figure 1. Plantmodel Editor - PM Agent
    Figure 2. CNS Editor - PM Agent - Editor
Note: Continue with the configuration of the PM-SERVER project. When creating a station for the project, use the link "https://[servername:portnumber]/ProcessManagement/PMServer/PMAgentOpenArchitecture" to establish a connection to WinCC OA .