Conformance statement

This section describes the Conformance statement for the WinCC OA IEC 61850 client.

ACSI Basic Conformance statement

Client/Subscriber Values/Comments
Client-Server role
B11

Server side (of TWO-PARTY APPLICATION-

ASSOCIATION)

-
B12

Client side of (TWO-PARTY APPLICATION-

ASSOCIATION)

C1 Yes
SCSMs supported
B21 SCSM: IEC 61850-8-1 used Yes ( MMS )
B22 SCSM: IEC 61850-9-1 used No
B23 SCSM: IEC 61850-9-2 used No
B24 SCSM: other Not Applicable
Generic substation event model (GSE)
B31 Publisher side -
B32 Subscriber side O No
Transmission of sampled value model (SVC)
B41 Publisher side -
B42 Subscriber side O No

LOGICAL-DEVICE model has been declared.

O – Optional

M – Mandatory

ACSI Models Conformance statement

Client/Subscriber Values/Comments
If Server side (B11) supported
M1 Logical device C2 Yes
M2 Logical node C3 Yes
M3 Data C4 Yes
M4 Data set C5 Yes
M5 Substitution O No
M6 Setting group control O No
Reporting
M7 Buffered report control O Yes
M7-1 sequence-number
M7-2 report-time-stamp
M7-3 report-time-inclusion
M7-4 data-set-name
M7-5 data-reference
M7-6 buffer-overflow
M7-7 EntryID
M7-8 BufTm
M7-9 IntgPd
M7-10 GI
M8 Unbuffered report control O Yes
M8-1 sequence-number
M8-2 report-time-stamp
M8-3 report-time-inclusion
M8-4 data-set-name
M8-5 data-reference
M8-6 buffer-overflow
M8-7 EntryID
M8-8 BufTm
M8-9 IntgPd
M8-10 GI
Logging O No
M9 Log control O No
M9-1 IntgPd
M10 Log O No
M11 Control M Yes
If GSE(B31/B32)is supported
M12 GOOSE O No
M12-1 EntryID
M12-3 DataReflnc
M13 GSSE O No
If SVC(B41/B42)is supported
M14 Multicast SVC O No
M15 Unicast SVC O No
M16 Time M Yes (through standard SNTP )
M17 File Transfer O Yes

c2 – shall be ‘M’ if support for the LOGICAL-NODE model has been declared.

c3 – shall be ‘M’ if support for the DATA model has been declared.

c4 – shall be ‘M’ if support for the DATA-SET, Substitution, Report, Log Control, or Time model has been declared.

c5 – shall be ‘M’ if support for the Report, GSE, or SV models has been declared.

M – Mandatory

ACSI Service

Services AA:TP/MC Client/Subscriber Comments
Server(Clause7)
S1 ServerDirectory TP Yes
Application association (Clause 8)
S1 Associate TP M Yes
S2 Abort TP M Yes
S3 Release TP M Yes
Logical device (Clause 9))
S5 LogicalDeviceDirectory TP M Yes
Logical node (Clause 10)
S6 GetLogicalNodeDirectory TP M Yes
S7 GetAlldataValues TP O Yes
Data (Clause 11)
S8 GetDataValues TP M Yes
S9 SetDataValues TP O Yes
S10 GetDataDirectory TP O Yes
S11 GetDataDefinition TP O Yes
Data set (Clause 12)
S12 GetDataSetValues TP O Yes
S13 SetDataSetValues TP O NO
S14 CreateDataSet TP O NO
S15 DeleteDataSet TP O NO
S16 GetDataSetDirectory TP O Yes
Setting group control (Clause 16)
S18 SelectActiveSG TP O NO
S1 SelectEditSG TP O NO
S1 SetEditSGValues TP O NO
S1 ConfirmEditSGValues TP O NO
S1 GetEditSGValues TP O NO
S1 GetSGCBValues TP O NO
Reporting (Clause 17)
Buffered report control ( BRCB )
S24 Report TP C6 Yes
S24-1 data-change(dchg)
S24-2 qchg-change(qchg)
S24-3 Data-Update(dupd)
S25 GetBRCBValues TP C6 Yes
S26 SetBRCBValues TP C6 Yes
Unbuffered report control ( URCB )
S27 Report TP C6 Yes
S27-1 data-change(dchg)
S27-2 qchg-change(qchg)
S27-3 Data-Update(dupd)
S28 GetBRCBValues TP C6 Yes
S29 SetBRCBValues TP C6 Yes
C6-shall declare support for at least one ( BRCB or URCB ).
Logging (Clause 17)
Log control block
S30 GetLCBValues TP M NO
S31 SetLCBValues TP O NO
Log
S32 QueryLogByTime TP C7 NO
S33 QueryLogAfter TP C7 NO
S34 GetLogStatusValues TP M NO
c7 – shall declare support for at least one (QueryLogByTime or Query LogAfter).
Generic substation event model( GSE)
GOOSE (Clause 18)
S35 SendGOOSEMessage MC C8 NO
S36 GetGOReference TP O NO
S37 GetGOOSEElementnumber TP O NO
S38 GetGoCBValues TP O NO
S39 SetGOCBValues TP O NO
GSSE (AnnexC)
S40 SendGOOSEMessage MC C8 NO
S41 GetGOReference TP O NO
S42 GetGOOSEElementnumber TP O NO
S43 GetGoCBValues TP O NO
S44 SetGOCBValues TP O NO
c8 – shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage).
Transmission of sample value model (SVC)(Clause 19)
Multicast SVC
S45 SendMSVMessage MC C10 NO
S46 GetMSVCBValues TP O NO
S47 SetMSVCBValues TP O NO
Unicast SVC
S48 SendUSVCBValues TP C10
S49 GetUSVCBValues TP O
S50 SetUSVCBValues TP O
c10 – shall declare support for at least one (SendMSVMessage or SendUSVMessage).
Control (Clause 20)
S51 Select M Yes
S52 SelectWithValue TP M Yes
S53 Cancel TP O Yes
S54 Operate TP M Yes
S55 Command-Termination TP M Yes
S56 TimeActivated-Operate TP O Yes
File Transfer (Clause 23)
S57 GetFile TP O Yes
S58 SetFile TP O NO
S59 DeleteFile TP O NO
S60 GetFileAttributeValues TP O NO
Time 5.5
T1 Time resolution of internal clock Nearest negative power of 2 in seconds
T2 Time accuracy of internal clock T0
T1
T2
T3
T4
T5
T3 Supported TimeStamp resolution Nearest value of 2**-n in seconds according to 6.1.2.9.3.2