Requirements and installation
Requirements
-
Correctly installed WinCC OA version 3.5 or higher.
-
ETM’s Cerberus Driver requires a Gateway MK7022 to send and receive messages to the C-Bus.
-
The usage requires a valid license!
For information on the supported platforms for the Cerberus driver see Supported Platforms of the most important Drivers.
Installation
A normal installation of WinCC OA version 3.5 is sufficient for using the Cerberus driver.
Under Windows it is required to run the Windows DOS-Box as administrator once before installing the Cerberus driver (Start->Accessories->right-click on Command prompt-> Run as administrator).
Restrictions
-
There can only be a maximum of 16 devices attached to the C-Bus.
In Intrusion: 1-CC440 control unit, 1-CK440 gateway, 14-CT4xx terminals.
In Fire: 4-CC11 control units, 12 - CT11 terminals (max. 11-CT11 , if the system includes a CK11 gateway).
-
The Cerberus driver does not work in redundant mode.
-
A Cerberus WinCC OA project cannot the stopped via PMON - therefore the 'net stop service name' must be used.