Jump to main content
BACnet
General
Driver |
Protocol |
Protocol standard / version |
Official protocol certification |
Included in Base License Package? |
Additional Licensing Requirements |
License Key (Code Meter) |
Operating System |
BACnet Driver |
BACnet |
ISO 16484-5 |
✔ |
❌ |
BACnet Objects |
Bacnet | BACnet Objects |
Windows | Linux |
Network
Driver |
Encrypted communication to periphery device |
Client Or Server / TCP or UDP |
Default Port |
Firewall Direction |
BACnet Driver |
❌ |
UDP |
47808
|
outbound | inbound |
Configuration Details
Driver |
Recommended/technical limit of connections per driver |
Multiple driver instances |
Redundant network |
Redundant devices |
Special hardware requirements |
BACnet Driver |
200 |
✔ (different port) |
❌ |
❌ |
❌ |
Communication
Driver |
Polling |
Poll on use |
Single query |
Unsolicited communication |
Driver redundancy: Only active driver polls |
Buffering |
BACnet Driver |
✔ |
✔ |
✔ |
✔ |
❌ |
✔ (TrendLog) |
Engineering
Driver |
Direct browsing of configuration/address data from connected
devices |
Import functionality of configuration/address data from external
tools |
Deletion of internal connection DP is
supported |
BACnet Driver |
✔ |
✔ (Import of EDE
file) |
✔ |
Special Telegrams
Driver |
Native alarm transfer from connected devices / PLCs |
Connection establishment without active address |
BACnet Driver |
✔ |
❌ |
Timestamps and Synchronization
Driver |
Timestamp transfer from periphery device |
Time synchronization (WinCC OA to PLC) |
BACnet Driver |
❌ |
✔ |